Galaxy Reader Wiring QRS

 

1.0 Wiegand Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.
  • Reader will require a separate power supply if current draw is over 150 mA.
  • Ground the drain-wire at one end only - at the DRM Board (GND) 
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • 635-DRM Board (PN 20-0235-10)

635-DRM Terminals (Function)

Wiegand Reader

LED     (LED control)

LED Control

D 1       (Data 1)

DATA 1

VDC    (+12 VDC)  *for +5VDC use Regulator PN 92-3001-05

VDC

GND    (Power Supply Ground)

GND

D 0       (Data 0)

DATA 0

 

2.0 ABA Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet. 
  • Reader will require a separate power supply if current draw is over 150 mA.
  • Ground the drain-wire at one end only  - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • 635-DRM Board (PN 20-0235-10)

 

635-DRM Terminals (Function)

ABA Reader

LED     (LED control )

LED Control

D 1       (Data 1)

DATA 1

VDC    (+12 VDC)  *for +5VDC use Regulator PN 92-3001-05

VDC

GND    (Power Supply Ground)

GND

D 0       (Clock Data)

CLOCK

back to top

 

3.0 Biometric Reader - Cable Specs & Wiring Pinout

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet.
  • Cat-5e Ethernet cable for TCP/IP communication back to the server; max cable distance 300 feet.
  • Reader will require a separate power supply if current draw is over 150 mA.
  • Ground the drain-wire at one end only  - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • 635-DRM Board (Dual Reader Module) – PN 20-0235-10

 

635-DRM Terminals (Function)

Wiegand Reader

LED      (LED control )

LED Control

D 1        (Data 1)

DATA 1

VDC     (+12 VDC)  *for +5VDC use Regulator PN 92-3001-05

VDC

GND     (Power Supply Ground)

GND

D 0        (Data 0)

DATA 0

 

back to top

 

4.0 MorphoTrak SIGMA Reader - Cable Specs & Wiring Pinout

  • 3-conductor, 20 - 24 AWG, overall shielded; non-stranded; max cable distance is 500 feet.
  • 2-conductor, 16 AWG (18 AWG) for power at +12VDC (+24VDC) for 500 feet. Reader draw 1A at 12v (0.5A at 24v).
  • Cat-5e Ethernet cable for TCP/IP server communication; max cable distance 300 feet.
  • Separate power supply required (current draw is 1A). Must common reader's p.s. ground to controller ground.
  • Ground the drain-wire at one end only  - land drain wire at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • 635-DRM Board (Dual Reader Module) – PN 20-0235-10
  • DRM Relay-2 is used to control Sigma “Wait for Panel Decision” for Voice/Prompt synchronization.

 

Reader Data Pinout

635-DRM Terminals (Function)

SIGMA Reader

LED     (LED control)

 

D 1       (Data 1)

WIEG DATA 1

VDC    (use separate p.s. for reader power)

VDC  (to separate power supply)

GND    (common the reader p.s. ground to Controller ground)

GND  (common to controller ground)

D 0       (Data 0)

WIEG DATA 0

 

635-DRM RELAY-2

SIGMA “Wait for Panel Decision”

COM    (must tie to ground of the reader’s power supply)

 - -

NO        (for voice/prompt control line)

WIEG LED1

 

NOTES:

  • For “Wait for Panel Decision”, connect Sigma LED1 to ‘NO’ leg of Relay-2. The 'COM' leg of Relay-2 must be tied to DRM GND.
  • Set Relay-2 for Timed Mode (1 to 2 secs) and “Valid Unlock” checkbox must be "checked" in System Galaxy Reader Properties.

 

back to top

 

5.0 Veridt Stealth Series Readers (NON-FICAM)

  • 5-conductor 22 AWG overall shielded; max cable distance 500 feet.
  • 2-conductor Twist pair, 22 AWG, max line distance 4000 feet (for RS-485 Comm. Mode/Factor Control).
  • Separate Power Supply required  (reader draws 400 mA at +12VDC).  Must common reader p.s. ground to controller ground.
  • Ground the drain-wire at one end only - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10
  • Min. Board Requirement: 635-DSI Board (Dual Serial Interface) – PN 20-0655-10  – required for Mode/Factor Control.

 

READER MODES/FACTORS

  • Mode 1 Card Only
  • Mode 2 Card + Pin
  • Mode 3 Card +Pin + Bio

 

635-DRM Terminals (Function)

Veridt Wiegand Reader

LED       (LED control)

LED Control   *required for correct operation

D 1         (Data 1)

DATA 1

VDC      (use separate p.s. for reader power)

VDC  (to separate power supply)

GND      (common the reader p.s. ground to Controller ground)

GND  (common to controller ground)

D 0         (Data 0)

DATA 0

 

 

635-DRM Terminals (Function)

Veridt RS-485 Comm

A +       (RS-485 Data)

Yellow wire

B –      (RS-485 Data)

Blue wire

 

NOTES:

  • DSI Section used for Mode/Factor Control must be set to “Veridt CAC Reader” in System Galaxy Serial Channel Properties.
  • LED Option must be set for Door Locked “Steady High” and Door Unlocked “Steady Low” in System Galaxy Loop Properties.

 

back to top

 

6.0 BridgePoint (NON-FICAM)

  • 5-conductor, 22 AWG, overall shielded; max. distance 200 Feet. (or 500 feet if pulling 18 AWG).
  • 2-conductor- twisted pair, 22 AWG max cable distance 500 feet.  (for Mode/Factor Control).
  • Separate Power Supply required  (reader draws 300 mA at +12VDC). Must common reader's p.s. ground to controller ground. 
  • Ground the drain-wire at one end only  - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10
  • DRM Relay-2 must be use for Mode/Factor Control. 

 

MODES/FACTORS:

  • Mode 1 Card Only
  • Mode 2 Card + Pin

 

635-DRM Terminals (Function)

BridgePoint Wiegand

LED      (LED control)

LED1  

D 1        (Data 1)

WEG 1

VDC     (use separate p.s. for reader power)

VDC  (to separate power supply)

GND     (common the reader p.s. ground to Controller ground)

GND  (common to controller ground)

D 0        (Data 0)

WEG 0

 

635-DRM RELAY-2 Terminals (Function)

BridgePoint Mode/Factor

COM    (must tie to ground of the reader’s power supply )

- -

NO        (to mode control line )

LED 2

 

NOTES:

  • Mode signal line High (unconnected) for 2-Factor Card + Pin.
  • Mode signal line Low (connected to ground) for 1-Factor Card Only
  • Place a schedule on Relay-2 in System Galaxy Reader Properties - to alternate Mode/Factor.  

 

back to top

 

7.0 SCM Readers (NON-FICAM)

  • 5-conductor, 22 AWG, overall shielded max cable distance 500 feet.
  • 2-conductor- twisted pair, 22 AWG, max cable distance 500 feet (for Mode/Factor Control).
  • Separate Power Supply required  (reader draws 300 mA at +12VDC).   Must common reader's p.s. ground to controller ground.
  • Ground the drain-wire at one end only  - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).
  • Min. Board Requirement: 635-DRM Board (Dual Reader Module) – PN 20-0235-10
  • DRM Relay-2 must be use for Mode/Factor Control. 

 

MODES/FACTORS

  • Mode 1 Card Only
  • Mode 2 Card + Pin

 

635-DRM Terminals (Function)

SCM Wiegand

LED      (LED control)

LED 1

D 1        (Data 1)

DATA 1

VDC     (Use separate p.s. for reader power)

VDC  (to separate power supply)

GND     (Common the reader p.s. ground to the controller ground)

GND  (common to controller ground)

D 0        (Data 0)

DATA 0

 

635-DRM RELAY-2 Terminals (Function)

SCM Mode/Factor

COM     (must tie to ground of the reader’s power supply )

REL 2

NO        (to mode control line )

RELGRN 

 

NOTES:

  • Mode signal line = High (unconnected) for 2-Factor Card + Pin.
  • Mode signal line = Low (connected to ground) for 1-Factor Card Only,
  • Place a schedule on Relay-2 in System Galaxy Reader Properties to alternate Mode/Factor.  

 

back to top

 

8.0 US GOV FICAM APL #

 

Contact Galaxy Control Systems for additional information about FICAM compliance.

 

 

Product

APL#

SUPPLIER

BridgePoint

10060

Galaxy Control Systems – PACS infrastructure

Veridt

10083

10084

Galaxy Control Systems – PACS infrastructure

Galaxy Control Systems – Validation System

HID

10097

10098

Galaxy Control Systems – PACS infrastructure

Galaxy Control Systems – Validation System

 

back to top

 

9.0 635-DRM (PN 20-0235-10) – Reader Pinout Full Section

There are two reader sections on a DRM Board. Each section has the following terminals …

READER WIRING (9-PIN CONNECTOR)

  • 5-conductor, 22 AWG, overall shielded; max cable distance is 500 feet. 
  • Reader may require separate power supply if the current draw is over 150 mA.
  • Ground the drain-wire at one end only  - at the DRM Board (GND).
  • Refer to reader manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

PINS

635-DRM Terminals (Function)

Wiegand

ABA

9

LED     (LED control line)

LED Control

LED Control

8

D 1       (Data 1)

DATA 1

DATA

7

VDC    (+12 VDC) *for +5VDC install Voltage Regulator PN 92-3001-05

VDC

VDC

6

GND    (Power Supply Ground )

GND

GND

5

D 0       (Data 0)

DATA 0

CLOCK

4

RLY      unused

 

 

DOOR CONTACT & REX MOTION DETECT (9-PIN CONNECTOR)

  • 2-conductor, 22 AWG, overall shielded (for Door Contact). 
  • 4-conductor, 22 AWG; overall shielded (for REX/Motion Detector). 
  • Separate Power Supply required for REX/Motion Sensor.
  • Ground all drain-wires at one end only  - at the DRM Board (GND).
  • Refer to device manufacturer’s instructions for wiring (manufacturer's specs may supersede Galaxy specs).

PINS

635-DRM Terminals (Function)

Device State

3

COM   (Common)

LED Control

2

CNT    (Door Contact)

NC  (Normally Closed Contact = Door Closed / Contact Closed)

1

REX    (Request to Exit - motion sensor)

NO  (Normally Closed Open = Momentary Push Button)

LOCK RELAY CONNECTOR (RLY-1)

  • 2-conductor, Minimum 18 AWG for Lock (Manufacturer’s specs for wire gauge may supersede Galaxy's). 
  • Separate Power Supply required for Lock - follow manufacturer's requirements for lock power supply.
  • Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)

635-DRM RELAY-1

LOCK DEVICE

COM

Land the lock wiring according to Manufacturer’s instructions.

NC = Normally Closed

NO = Normally Open

RELAY-2 CONNECTOR – OPTIONAL OUTPUT

  • For optional output (i.e. piezo, bell, buzzer ...)
  • Relay is Form-C SPDT Dry, (Rated max. 24v, 1.5 Amps)
  • Relay-2 (mode/timers/event-triggers) must be configured for desired behavior in SG Reader Properties.

635-DRM RELAY-2

OUTPUT DEVICE

COM

Land the lock wiring according to Manufacturer’s instructions.

NC = Normally Closed

NO = Normally Open

SG Rly2 Modes (set timers appropriately)

Available Events   (

will vary by selected Mode)

  • FOLLOWS
  • Door Forced Open
  • Valid Unlock
  • TIMED
  • Door Open Too Long
  • Duress
  • SCHEDULED
  • Invalid Access Attempt
  • PassBack
  • LATCHED

 

 

 back to top